Description

Product Description

TECHNICAL SPECIFICATIONS

Model

E002GER31

Phase

Single phase with ground

Capacity

2000 VA / 2000 W

INPUT

Nominal Voltage

100/110/115/120 /127 VAC or 200/208/220/230/240 VAC

Voltage Range

55-150 VAC ± 5% or 110-300 VAC ± 5% @ 50% Load, 80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% Load

Frequency Range

40Hz ~ 70Hz

Harmonic Distortion(THDi)

≦5% @ Nominal Input Voltage

Power Factor

≧ 0.99 @ Nominal Voltage (100% load)

OUTPUT

Output Voltage

100*/110*/115*/120/127 VAC or 200*/208*/220/230/240 VAC

AC Voltage Regulation (Batt.
Mode)

± 1%

Frequency Range (Synchronized Range)

57 ~ 63 Hz or 47 ~ 53 Hz

Frequency Range
(Batt. Mode)

60Hz ± 0.1Hz or 50 Hz ± 0.1Hz

Current Crest Ratio

3:1 (max.)

Harmonic Distortion

≦ 2 % THD (Linear Load); ≦ 4 % THD (Non-Linear Load)

Transfer Time – AC Mode to Battery Mode

Zero

Transfer Time – Inverter to Bypass

4 ms (Typical)

Waveform (Batt. Mode)

Pure Sinewave

EFFICIENCY

AC Mode

≧91% @ Full Charged Battery

ECO Mode

≧ 96% @ Full Charged Battery

Battery Mode

≧90%

BATTERY

Battery Type

12 V / 9 AH – 12 V / 7 AH

Numbers

4 – 6

Typical Recharge Time

3 Hours Recover to 95% Capacity for Internal Battery@ 2A Charging Current

Charging Current

100/110/115/120 /127 VAC Models: Default 2A, Max. 8A Adjustable
200/208/220/230/240 VAC Models: Default 2A, Max. 12A Adjustable

Charging Voltage

54.8 VDC ±1% – 82.1 VDC ±1%

PHYSICAL

Dimension, D X W X H (mm)

510 x 438 x 88 – 630 x 438 x 88

Net Weight (without battery) (kgs)

9.4 – 10.6

Net Weight (with battery) (kgs)

19.5 – 23.3

ENVIRONMENT

Humidity

20-90 % RH @ 0- 40°C (Non-Condensing)

Noise Level

Less than 50dBA @ 1 Meter

Altitude

10% de-rating for over 1000m (The altitude should not exceed 3000m)

MANAGEMENT

Smart RS-232 / USB

Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux and MAC

Optional SNMP

Power management from SNMP manager and web browser